Siata Filox R Water Filter

Price range: £150.00 through £4,170.00

Media

  • Type Filox R (75% – 85% Manganese Dioxide)
  • Life Span Dependent on frequency of backwashing and site conditions

Download our Filox R Media Filter Guide for more information.

Please note All our SIATA vessels are structural fibre certified, with Purolite or Dow resin. Please be aware of inferior products elsewhere.

General Conditions for Installation

  • Connection Inlet & Outlet:
    • V132F 1"
    • V230F 1¼" Union
    • V250F  1" Union
  • Electrical Rating: 230-12V / 50 Hz
  • Power Rating: 4.6VA
  • Minimum Inlet Pressure: 200 kPa ( 2 Bar )
  • Maximum Inlet Pressure: 700 kPa ( 7 Bar )
  • Vacuum: Not permitted
  • Average Pressure Loss: 100 kPa ( 1 Bar )
  • Maximum Water Temperature: 43° C
  • Operating pH Range: 5.0 - 9.0
  • Screen Size: 12 x 40
  • Removal Capacity @ Exhaustion:
    • Iron 27 ppm
    • Manganese 11 ppm
    • Hydrogen Sulfide 17 ppm
- +
SKU N/A Categories ,

Dimensions (mm)

Model referenceValve H1Vessel H2Vessel B1Filter HtInlet/outletDrawing no.
SIF132SFEC10FR195138725715821"Fig. 1
SIF132SFEC13FR195137433415691"Fig. 1
SIF230SFEC14FR195166036918551¼"Fig. 1
SIF250SFEC16FR370166040620301½"Fig. 2
SIF250SFEC18FR370175046921201½"Fig. 2
SIF250SFEC21FR37016405522010Fig. 2
SIF351SFEC24FR26018906102150Fig. 3
SIF351SFEC30FR26023007702560Fig. 3
SIF363SFEC36FRn/a235092725502" SM*Fig. 4

* SM denotes side mounted valve

Regeneration

Start: Programmable regeneration time + day interval

Manual: Manual operation as required

Specifications

Vessel Diameter10″13″14″16″18″
Media Volume Cu ft122.545
Service flow rate m³/hr0.91.82.23.64.5
Backwash flow rate m³/hr1.83.13.54.75.9
Vessel Diameter21″24″30″36″
Media Volume cu ft681116
Service flow rate m³/hr5.47.21014.5
Backwash flow rate m³/hr8.811.81624