Limitent Water Hardness Monitor

Price range: £70.00 through £865.00

Automatic hardness monitoring unit for installation after water softeners. The unit is designed for continuously monitoring the soft water quality without consumption of neither chemicals nor water. In case of hardness breakthrough, a LED signalizes ‘hard water’. An output for a malfunction alarm signal and/or the shut-down of a downstream reverse osmosis unit is provided.

The differential pressure valve which is installed in the soft water line creates a slight difference in the water pressure. Therefore part of the water passes through a bypass an the hardness sensor which is mounted there before return to the main stream. In case of hard water leakage the sensor will be charged which makes the special resin contained therein shrink. The transmitter with Reed contact activates the optical alarm signal ‘hard water’. The potential-free contact can be used to emit an optical or acoustic signal  and/or shut-off the reverse osmosis unit.

Features

  •  Automatic hardness monitoring unit for continuous control of the soft water downstream of water softening units
  •  General fault signal as potential-free change-over contact in the event of hardness breakthrough, e.g. to switch off a downstream reverse osmosis unit
  •  No need for water or chemicals, since no regeneration
  • differential pressure valve
  • hardness sensor on a resin expansion/shrinkage base
  • replacement sensor
  • shut-off valves
  • connecting tubes
  • transmitter unit with Reed contact
  • control
- +

Mounting

  •  Install hose an fittings in soft water line
  • Observe direction of water flow
  • Mount PVC panel vertically to wall nearby.
  • Connect hoses as shown on enclosed drawing.
  • Connect additional control functions at the terminals 1-2-3 (potential-free contact) in the control unit.

Start-Up

  • Make sure that soft water is available.
  • Connect to 230V/50Hz outlet. The light ‘operation’ resp. ‘Betrieb’ is on.
  • Slowly open both shuth-off valves and check that joints do not leak.

What to do in case of ‘hard water’ alarm

  •  Close shut-off valves (angle valves) at top and bottom.
  •  Unscrew and exchange sensor.
  • Before rerun make sure that soft water is available. Do not open inlet valve to limitent if soft water is not available.

Attention: The replacement sensor must be rinsed with soft water before installation. It should be kept humid during storage.

Maintenance
Sensor must be changed one time a year

Connection SizeInch¾"1"1¼"1½"2"
Max Flow Ratem³/h2.57.012.016.025.0
Min Flow Ratem³/h0.0250.20.51.53.0
Max Pressure Dropbar0.20.20.20.20.2
Min/Max Feedwater Pressurebar2/62/62/62/62/6
Min/max Feedwater Temperature°C5/355/355/355/355/35
Max Ambient Temperature°C4040404040
Power SupplyV/Hz230/50230/50230/50230/50230/50
Changeover Contactsfloatingfloatingfloatingfloatingfloating
Max LoadV/A/W250/5/600250/5/600250/5/600250/5/600250/5/600