For desalination of softened drinking water according to drinking water regulations (free chlorine not detectable). Compact system with a small footprint suitable for wall mounting or fixation on the floor.

Item NamePermeate Flow l/hMembranes
UO 1201204021 X 1
UO 3003004040 X 1
UO 5005004040 X 2

Features

  • Wall mounted or free standing
  • Particularly space saving (420 x 350 x 1300mm)
  • RO 524 controller
  • Recovery from 75% to 80%
  • Salt rejection percentage: min. 97%
  • Working pressure: 12 bar
  • Voltage: 230 V/50 Hz
  • Analogue flow meters

General Conditions for Installation

Controller :RO 524

  • Desalination rate min.:97 %
  • Permeate recovery:75 – 80 %
  • Permeate back pressure max.:0.3 bar
  • pH value operation:6.5 – 9.5
  • pH value cleaning:2 – 12
  • Ambient temperature:5 – 40 °C

Conditions of use: The unit may only be used for the desalination of softened feed water with drinking water quality or appropriately pre-treated well or surface water. The unit is designed for a salinity (TDS) of 1,000 mg/l and a temperature of 15 °C. Under these conditions, the projected permeate output is achieved even after three years of operation. The permeate yield depends on the raw water quality and the pre-treatment. The following parameters must be maintained in the feed water:

  • Free chlorine:not detectable
  • Iron (Fe):< 0.2 mg/lManganese (Mn):< 0.05 mg/l
  • Silica (SiO2):< 25 mg/lSilt density index (SDI):< 3
  • Feed water temperature:5 – 35 °C
  • Feed water pressure:3 – 6 barPressure fluctuation:± 0.5 bar
- +